Viessmann · Boiler troubleshooting

Connect cascade via CAN bus

Vitocrossal 200 CI2

What is going on

Connect the previous and following heat generator cables to plug lA. Wrong connection causes malfunctions.

Likely causes

  • Incorrect polarity
  • Wrong cable size

Check in this order

  1. Use 2-wire cable, minimum 24 AWG.
  2. Loosen the terminal screws, insert the cores, and tighten.
  3. Check polarity.
  4. Set CAN bus terminator switch A as per its setting table.

Applies to: CAN bus plug lA

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 200 CI2 Installation Instructions, p. 28. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.