Viessmann · Boiler troubleshooting
Clean the combustion chamber and heat exchanger
What is going on
Periodic cleaning of the combustion chamber and heating surfaces after the burner is removed. Use only non-metallic tools and a cleaner that is safe for the heat exchanger and refractory.
Check in this order
- Perform a gas leak test when the job is finished.
- Follow the cleaning agent maker's safety instructions and wear proper protective gear.
- Do not use a metal wire brush or powered wire brushes.
- Remove the burner assembly (see burner removal on p. 22).
- Vacuum loose debris out of the combustion chamber.
- Rinse embedded sediment off the heat exchanger with water or a solvent-free cleaner such as a citric acid based product. Keep water off the refractory.
- Discoloration of the heat exchanger is normal and does not affect function or service life.
- If needed, brush gently with a non-metallic brush to loosen embedded sediment.
- Flush the combustion chamber with water until it runs clear through the condensate trap.
- Empty and clean any debris from the condensate trap, then reinstall it (see p. 25).
- Refit the burner and tighten the nuts diagonally to 3 lb.ft (4 Nm).
- Fit the gas supply pipe with a new gasket and tighten to 11 lb.ft (15 Nm).
- Plug in the air intake adaptor.
- Reconnect the electrical leads to their components.
Applies to: Vitocrossal 300 CU3A 26 to 199
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 24. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.