Weil-McLain · Boiler troubleshooting
Remove, inspect and clean the burner
What is going on
Burner is ceramic fiber and must be handled with care. Clean by vacuum or water flush only.
Likely causes
- Lint or sediment in the burner
- Damaged burner insulation
- Damaged or stretched gaskets
Check in this order
- Use an 8 mm wrench or socket to remove the five M5 bolts holding the burner access hatch
- Remove the burner access hatch
- Use a 10 mm socket or wrench to remove the six M5 bolts securing the burner
- Pull the burner straight up and out; do not angle it, since that can damage the insulation
- Remove and discard the burner gasket
- Inspect the burner access hatch seal; if damaged, discard and use a new seal on reassembly
- Inspect the inside of the burner and brush or vacuum lint or sediment, or clean with a water spray from inside
- Inspect the burner exterior for damage
- Clean the underside of the burner flange with a soft brush to remove gasket fragments
- Set the burner aside and let it dry completely before reinstalling
- If insulation is damaged, replace it; if fragments fell into the heat exchanger, clean the heat exchanger thoroughly
- Replace any damaged or stretched gaskets before returning the boiler to service
Applies to: SVF 500/600 Series 1 boiler
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SVF 500/600 Series 1 boiler manual, p. 110. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.