Direct exhaust sidewall termination location
What is going on
Sidewall terminations must meet the location rules in the code and the clearances in Figure 27.
Check in this order
- Keep vent and air terminations at least 12 in above grade and snow line.
- Keep a minimum of 4 ft horizontally from electrical meters, gas meters, regulators and relief equipment.
- Do not install the termination above or below meters, regulators or relief equipment.
- Do not terminate above a door or window or above a public walkway, where condensate can freeze or drop on people.
- Avoid locations where wind eddies can recirculate exhaust.
- Check the local gas code (NFPA 54 or CAN/CSA B149.1) for minimum distances to openings and buildings.
Applies to: Direct exhaust sidewall termination, Category IV
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SVF 500/600 Series 1 Boiler Manual, p. 43. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.