Weil-McLain · Boiler troubleshooting

Direct exhaust sidewall termination location

SVF 500/600 Series 1

What is going on

Sidewall terminations must meet the location rules in the code and the clearances in Figure 27.

Check in this order

  1. Keep vent and air terminations at least 12 in above grade and snow line.
  2. Keep a minimum of 4 ft horizontally from electrical meters, gas meters, regulators and relief equipment.
  3. Do not install the termination above or below meters, regulators or relief equipment.
  4. Do not terminate above a door or window or above a public walkway, where condensate can freeze or drop on people.
  5. Avoid locations where wind eddies can recirculate exhaust.
  6. Check the local gas code (NFPA 54 or CAN/CSA B149.1) for minimum distances to openings and buildings.

Applies to: Direct exhaust sidewall termination, Category IV

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF 500/600 Series 1 Boiler Manual, p. 43. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.