Multiple zones with zone valves (24 V and isolation relay)

CGi Series 5

What is going on

Zone valves need a separate 24 V transformer sized for the total load of all valves. Do not wire 3-wire zone valves directly to the boiler T-T terminals. Use an isolation relay, which can damage boiler parts or cause unreliable operation if skipped.

Likely causes

  • 3-wire zone valves wired directly to T-T terminals

Check in this order

  1. Install isolation (balancing) valves to balance the zones.
  2. Provide a separate 24 V transformer and size it for all zone valves connected.
  3. Do not wire 3-wire zone valves directly to the boiler T-T terminals.
  4. Install an isolation relay for 3-wire zone valves.
  5. Wire the zone valve end switch wires to the isolation relay coil.
  6. Wire the isolation relay contact across the boiler T-T terminals.

Applies to: CGi-25 to CGi-8

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: CGi Series 5 boiler manual, p. 30. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.