Example D control setup and circulator supply
What is going on
The required settings are in Table 7, which is not on these pages. The ODT setpoint and the activate contact below setpoint must match the design conditions of the system. Unlike Example C, the boiler circulator must be supplied by the installer.
Check in this order
- Make settings with the WIZARD or with the manual menu steps elsewhere in the manual.
- Set the ODT setpoint to the system design outdoor temperature.
- Set the activate contact below setpoint to the system design condition.
- Supply the boiler circulator and follow all piping instructions for the boiler and system.
- Check FLA, locked rotor and inrush for the boiler and system circulators against the relay limits.
Applies to: Example D multi-boiler with high-mass boiler
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Series 2 Condensing Gas Boiler Advanced Manual, p. 32. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.