Replacing the printed circuit board (cascade electronics)

Vitotronic 300-K MW1S

What is going on

Replacement of the cascade electronics printed circuit board. Record and restore settings.

Check in this order

  1. Record all coding and adjustments made at the control unit.
  2. Replace the printed circuit board.
  3. Set coding 8A to 176.
  4. Set coding address 92 to 92:160.
  5. Re-enter the recorded coding and adjustments.

Applies to: Vitotronic 300-K MW1S cascade electronics module A2

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300-K MW1S installation and service instructions, p. 119. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.