Wire combustion air blower through adaptor
What is going on
Blower is powered through the combustion air device adaptor and needs a proving switch.
Check in this order
- Disconnect power to control and burners.
- Install combustion air device adaptor (Part No. 7134 563) on the DIN rail in the connection enclosure, or in the boiler junction box on CM2.
- Connect the blower to the adaptor 120 VAC, max 5 FLA, use AWG 14 wire.
- Connect the proving switch (normally open, rated 120 VAC) as shown in the diagram.
- Provide disconnect means and overcurrent protection as required by local codes.
- Confirm the blower is suitable for this application.
Applies to: VD2/VD2A/CT3 and CM2 boilers
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitotronic 300 GW2 installation and service instructions, p. 45-46. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.