Weil-McLain · Boiler troubleshooting
Expansion tank installation
What is going on
Expansion tank sizing and location must keep the system from losing water through the relief valve.
Likely causes
- Undersized tank lets water blow out the relief valve and makeup water feed in through the fill valve.
- Leaks in the tank piping let air escape and waterlog the tank.
Check in this order
- Size the tank for boiler and system water volume and temperature.
- Locate the cold water fill connection at the expansion tank, never elsewhere.
- Install an automatic air vent on top of the air separator for diaphragm or bladder tanks only.
- Do not use an automatic air vent with a closed-type tank.
- Do not use a closed-type tank if connecting to a water heater that has an automatic air vent.
- Slope horizontal piping at least 1 inch per 5 feet.
- Use a tank fitting such as a B&G Tank-trol or Taco-trol on closed-type tanks.
- Correct all leaks in the system or tank piping.
Applies to: Heating system expansion tank
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec Series 3 boiler manual, p. 54, 55. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.