Weil-McLain · Boiler troubleshooting

Expansion tank installation

ECO Tec Series 3

What is going on

Expansion tank sizing and location must keep the system from losing water through the relief valve.

Likely causes

  • Undersized tank lets water blow out the relief valve and makeup water feed in through the fill valve.
  • Leaks in the tank piping let air escape and waterlog the tank.

Check in this order

  1. Size the tank for boiler and system water volume and temperature.
  2. Locate the cold water fill connection at the expansion tank, never elsewhere.
  3. Install an automatic air vent on top of the air separator for diaphragm or bladder tanks only.
  4. Do not use an automatic air vent with a closed-type tank.
  5. Do not use a closed-type tank if connecting to a water heater that has an automatic air vent.
  6. Slope horizontal piping at least 1 inch per 5 feet.
  7. Use a tank fitting such as a B&G Tank-trol or Taco-trol on closed-type tanks.
  8. Correct all leaks in the system or tank piping.

Applies to: Heating system expansion tank

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec Series 3 boiler manual, p. 54, 55. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.