Weil-McLain · Boiler troubleshooting
Choosing direct exhaust or direct vent
What is going on
Direct exhaust takes combustion air from inside the boiler room, and the air piping is not connected to the air inlet. Direct vent pipes combustion air in from outside. Category II is a negative-pressure vent and requires direct exhaust. Category IV is a positive-pressure vent and can use either method.
Check in this order
- Direct exhaust supply combustion air through openings into the boiler room, sized per this manual and code.
- Where the boiler shares a space with other appliances, size the combustion air openings for the combined load of all appliances.
- Direct vent pipe combustion air from outside, keeping the air inlet away from any source of contamination listed in Table 7.
- Combustion air may be piped individually per boiler, or manifolded (Figure 25, p. 40).
- Combustion and ventilation openings may also be required in boiler room walls per this manual and code.
Applies to: SVF 500/600 boilers, Category II and Category IV
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SVF 500/600 Series 1 Boiler Manual, p. 29. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.