Weil-McLain · Boiler troubleshooting

Zoning with WMZV zone valve controller plus DHW controlled by boiler

SlimFit Series 3

What is going on

Zone controller call on Input 2, DHW aquastat on Input 1. The system circulator on Output 2 runs on any zone call.

Check in this order

  1. The system must have a by-pass pressure regulating valve, because flow can occur with zone valves closed.
  2. Review the 120 VAC output wiring (p. 60) and 24 VAC input wiring (p. 52).
  3. Connect the zone controller call (X-X) to Input 2 on PRIORITY 2 and choose the space heating system type.
  4. Wire the system circulator to Output 2. It turns on for any zone controller call for heat.
  5. Connect the DHW aquastat to Input 1 and assign Input 1 to PRIORITY 1. Wire the DHW circulator to Output 1.
  6. Use the factory defaults for DHW and the heating system type, or change if needed.

Applies to: SlimFit Series 3 with WMZV zone valve controller

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain SlimFit Series 3 boiler manual, p. 65. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.