Indirect DHW aquastat wiring for priority
What is going on
Heat only and combi models use different inputs for indirect DHW.
Check in this order
- Heat only connect the DHW aquastat to any one of the four input and output pairs. Assign it to PRIORITY 1 in the WIZARD or System Settings menu.
- Combi connect the DHW aquastat to Input 2 or Input 3. Assign it to PRIORITY 2 in the WIZARD or System Settings menu.
- On combi, the internal combi DHW is PRIORITY 1 and the indirect tank is PRIORITY 2.
Applies to: ECO Tec Series 3 heat only and combi models
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec series 3 condensing gas boiler boiler manual, p. 68-69. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.