Viessmann · Boiler troubleshooting

Fixed high limit test #1 (F2 simulation with boiler pump disconnected)

Vitodens 200-W B2HB

What is going on

Test that trips the manual reset high limit by running the burner with the boiler pump disconnected. Viessmann is not responsible for damage caused by overheating during this test.

Check in this order

  1. Make sure the boiler and boiler pump are in normal operating condition.
  2. Remove the cover at the back of the boiler control to reach the control plugs.
  3. In the extended menu, select Test mode, then flue gas test ON, and press OK.
  4. Wait for the burner to ignite and go to high fire.
  5. Once the burner is lit, unplug the boiler pump from the control board carefully.
  6. Watch the boiler temperature rise. The burner shuts off and the temperature should keep climbing.
  7. At about 210°F (99°C) the limit trips and shows F2.
  8. If the limit is not reached, wait two minutes after burner shutoff, then energize the pump for no more than 1 second. Repeat as needed.
  9. For boilers with flow switches (sizes 19 to 100), the switches may need to be jumpered during the test.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitodens 200-W B2HB 45, 57, 160, 199 service instructions, p. 8. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.