Viessmann · Boiler troubleshooting

Fit the control unit top section

Vitotronic 300

What is going on

Assemble the top of the control unit onto the bottom and secure the hinged support bar.

Check in this order

  1. Install the rear control housing.
  2. Position the top of the control unit on the bottom and snap together.
  3. Cut through the sticker, pull out the hinged support bar and pull down until the lower section snaps in.
  4. Snap the end of the support bar into the holding clip at the bottom of the control.
  5. Insert the flat cable connector in plug-in location X10 and lay the cable under the holding clip.
  6. Unlock the support bar by pressing the linkage point, then bring the top down until it snaps into the bottom.

Applies to: Vitotronic 300 KW3

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300 installation instructions, p. 23. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.