Install auxiliary low gas pressure switch
What is going on
Fit and wire the auxiliary low gas pressure switch on the gas line, then set it and leak test.
Check in this order
- Disconnect boiler power.
- If the boiler is already installed, shut off the main gas supply and disconnect the gas piping.
- Install the gas piping components as required.
- Route the cable under the top rail and secure it with plug-in cable retainers.
- Wire the switch green to ground G, white to 26 (L) COM, black to 27 (L) NO.
- Set the low gas pressure switch to 4.5 in. w.c.
- Open the gas supply to the burner.
- Leak test the gas line and the switch with an approved gas leak detector.
- Reconnect boiler power.
Applies to: Auxiliary low gas pressure switch
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 200 CM2 186 to 311 service instructions, p. 27. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.