Multiple boilers with an isolation heat exchanger: when to use it

Ultra Series 4

What is going on

Use an isolation heat exchanger for large systems with high mineral content in the water, systems fed with untreated makeup water, old systems heavily scaled or rusted inside piping and heat units, process applications, commercial service water, and high-pressure systems that need a heating-system relief setting above 30 PSIG (tall buildings).

Check in this order

  1. Size the heat exchanger with the exchanger manufacturer.
  2. Pipe the exchanger shell side and tube side per the manufacturer. Tube-side flow and temperature must meet the heating system requirements.
  3. Give the heat exchanger shell-side circuit its own expansion tank.
  4. Give the heating system circuit its own expansion tank and its own relief valve, set to protect the system and the exchanger piping.
  5. Strap supply and return sensors to the lines at least 6 pipe diameters, but no more than 3 feet, from the boiler connection tees.
  6. Install a flow/check valve and boiler circulator on each boiler, and run each boiler relief valve discharge per the Ultra boiler manual.
  7. If individual isolation valves are used, individual boiler level controls may be needed.

Applies to: Multiple Ultra boilers on isolation heat exchanger piping

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Ultra Series 4 boiler manual, p. 64. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.