Viessmann · Boiler troubleshooting
Check gas side connections for leaks
What is going on
Use new gaskets on all gas fittings separated on site. Do not use leak detection spray near electrical contacts, as it can cause faulty operation.
Likely causes
- Gas fitting gasket leak
Check in this order
- Insert new gaskets in all gas fittings separated on site.
- Open the gas shut-off valve.
- Check the sealing points of the gas solenoid valve for leaks.
- Start the burner (see page 25).
- Check the outlet sealing points of the gas solenoid valve.
- Check the sealing point between the fan and the burner plate.
- Check the sealing point between the fan and the Venturi pipe.
Applies to: Vitocrossal 200 CI2 boilers
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 200 CI2 Service Instructions, p. 34. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.