Annual service inspection steps
What is going on
Routine checks that go with the annual startup. Electrical power must be off before service, except where the manual states otherwise.
Likely causes
- Debris on the air inlet screen
- Debris or sediment in the condensate trap
- Blocked or leaking air intake or vent
Check in this order
- Turn off power to the boiler before service.
- Confirm the area is free of combustibles and flammable vapours.
- Confirm the air intake is free of contaminants listed on page 24.
- For direct vent installations, remove the cover from the air pipe inspection tee and check the air inlet box screen with a mirror if needed.
- Vacuum debris off the screen and brush gently with a soft brush if needed.
- Refit the tee cover when complete.
- Clean the condensate trap if debris has collected, then refit with a gasket and tighten the clamps.
- Check all water and gas piping for leaks and check gas line per page 45.
- Confirm combustion and ventilation air openings are clear, and check automatic dampers if fitted.
- Inspect the full flue and air piping for blockage, deterioration or leaks, and repair per vent manufacturer instructions.
Applies to: SlimFit Series 2 annual service
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 88. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.