Weil-McLain · Boiler troubleshooting

Gas valve adjustment at low fire (offset)

SVF Series 1

What is going on

Only for a qualified technician. Check low fire after high fire has been set.

Check in this order

  1. Lock the boiler at low fire in Manual Test Mode.
  2. Confirm the displayed blower rpm matches the low fire value in the table.
  3. Check CO2 at low fire.
  4. If low fire is not acceptable, use a 2.5 mm Allen wrench on the offset adjustment.
  5. Turn toward plus to raise CO2 or toward minus to lower it. Use 1/2 turn, then back off 1/4 turn.
  6. Re-check high fire, then low fire, and repeat until both meet the CO2 values.
  7. Return the firing rate to Auto.
  8. If both cannot be met, contact Weil-McLain.

Applies to: SVF 1500-3000

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF Series 1 boiler manual, p. 89. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.