Combustion check at high and low fire

Ultra Series 4

What is going on

Check flame and combustion with calibrated instruments at high and low fire.

Likely causes

  • Throttle screw position out of range
  • Gas input off rating

Check in this order

  1. Start a call for heat on one heat demand input.
  2. Enter installer menus and force firing rate to MAX (high fire).
  3. Look through the flame inspection window flame should be blue and stable with the burner surface covered in orange dots.
  4. Remove the flue temperature sensor and insert a combustion test probe.
  5. Test CO2 (or O2) and CO. CO2 must be within 1.0% of the values in Figure 42, page 41.
  6. If out of range, adjust the throttle screw as described on page 41.
  7. Measure natural gas input (see gas input tip) and compare with the boiler rating label.
  8. Force firing rate to MIN (low fire); flame should be stable, evenly spread, with uniform orange colour. Repeat the CO2 and CO test.
  9. Force firing rate back to AUTO.
  10. Refit the flue gas sensor insert the rubber grommet into the flue pipe, then insert the probe into the grommet.

Applies to: Ultra Series 4 gas boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain Ultra Series 4 boiler manual, p. 40. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.