Rinnai · Boiler troubleshooting

First-time settings using Bluetooth (recommended)

I-Series Plus

What is going on

Sets gas type and venting from a phone or tablet with the Rinnai Central app. The boiler is set for natural gas and PVC venting as default, so these must be confirmed before firing.

Check in this order

  1. Power the boiler for the first time. The display shows SEt and the Maintenance Mode icon blinks.
  2. Use a device with Bluetooth 4.0 or newer.
  3. Open the Rinnai Central app and log in with a professional account.
  4. Press the Bluetooth button on the controller until its LED stays solid.
  5. Tap Connect to a Rinnai Boiler in the app. Wait for the pairing beep.
  6. Confirm or change settings in the app.
  7. When finished, the display returns to normal operating status.

Applies to: I-Series Plus condensing combi boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rinnai I-Series Plus IP060160C installation manual, p. 65. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.