Viessmann · Boiler troubleshooting
Replace motorized burner inlet damper
What is going on
Removal of the motorized damper together with its servomotor and linkage. Equipped on CM2 246 and 311 only.
Check in this order
- Remove the four screws that hold the damper to the venturi tube and remove the damper with servomotor and linkage.
- Remove the servomotor cover.
- Unplug the servomotor.
- Disconnect the linkage from the servomotor shaft. Remove the bolts and the servomotor.
- Refit the servomotor, linkage and damper.
- Make sure the damper vents are fully open. Adjust the linkage if needed.
- Tighten to the torque in the torque table and reassemble in reverse order.
Applies to: CM2 246 and 311
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 37. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.