Application 3: single fixed-setpoint zone with no pump output

Vitocrossal 300 CU3A

What is going on

Single-temperature zone. A thermostat call goes through the multi-zone control to the DE1 input of the EA1 boiler, which then runs a fixed zone setpoint. No pump is assigned to this zone.

Check in this order

  1. In the zone control wizard, select 1 Zone Circuit and press OK.
  2. Confirm the fixed setpoint choice and press OK.
  3. Leave the pump unassigned. Pressing OK without choosing an output assigns no pump.
  4. Check that the zone circuit summary shows no pumps selected.
  5. Finish start-up when the boiler reports it is ready.
  6. Set the target water temperature for a heat call with the arrow keys and press OK.

Applies to: Application 3, one zone circuit, no pump output

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CU3A Application Guide, p. 28. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.