Viessmann · Boiler troubleshooting
Application 3: single fixed-setpoint zone with no pump output
What is going on
Single-temperature zone. A thermostat call goes through the multi-zone control to the DE1 input of the EA1 boiler, which then runs a fixed zone setpoint. No pump is assigned to this zone.
Check in this order
- In the zone control wizard, select 1 Zone Circuit and press OK.
- Confirm the fixed setpoint choice and press OK.
- Leave the pump unassigned. Pressing OK without choosing an output assigns no pump.
- Check that the zone circuit summary shows no pumps selected.
- Finish start-up when the boiler reports it is ready.
- Set the target water temperature for a heat call with the arrow keys and press OK.
Applies to: Application 3, one zone circuit, no pump output
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CU3A Application Guide, p. 28. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.