NaviClean magnetic filter: annual service
What is going on
NaviClean is an in-line magnetic/dirt filter (made by ADEY) for hydronic systems. Best spot is after the last zone and before the boiler. It needs a yearly clean.
Likely causes
- Magnetite and debris build-up in the filter
Check in this order
- It holds pressure and can be hot. Let it cool and release pressure before opening.
- Strong magnet keep it away from phones and cards. Careful if you have a pacemaker.
- Turn both valves off.
- Open the vent to release pressure.
- Open the drain and let the debris out, then close it.
- Remove the cover and clean out the inside.
- Refit the cover. Do not overtighten.
- Turn the valves on, open the vent to bleed air, then close it.
- Optional add ADEY MC1+ inhibitor through the filter.
- Limits 87 psi max, 203°F max, up to 21 GPM. Connections 1 in. compression or 1-1/4 in. NPT adapters.
Applies to: Navien NaviClean hydronic filter
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: NaviClean Installation and Service Manual 1807 (Navien / ADEY), p.1-2. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.