Viessmann · Boiler troubleshooting

Burner calibration and combustion analysis

Vitorond 100

What is going on

Verify factory burner settings at the final site with calibrated combustion equipment and adjust for local conditions.

Check in this order

  1. Use only calibrated flue gas analyzer equipment.
  2. Measure CO2, stack temperature, draft and CO in the flue pipe between the boiler and the barometric draft regulator, before dilution air.
  3. Measure over-fire draft at the combustion chamber observation port.
  4. Adjust the burner so combustion meets the targets for the local installation.
  5. Never adjust the burner by eye.
  6. Do not tamper with the unit or controls.

Applies to: All VR1 models

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitorond 100 installation and service manual, p. 40, p. 48. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.