Viessmann · Boiler troubleshooting
Hydronic piping layout and safety header
What is going on
Piping rules for the boiler water connections.
Check in this order
- Locate the safety header on the main supply header.
- Install the supplied air vent and pressure relief valve on the supply header. An alternate PRV location is the boiler supply line.
- Connect the precharged expansion tank and any automatic feed water to the boiler return.
- Install the boiler pump on the return pipe so it pumps water into the boiler.
- Install the supplied low water cut-off directly on the safety header or in the piping above the pressure vessel.
- Close off all unused connections that are not used for water or controls.
- Make all connections free of load and torque stress.
- Do not connect the heating system to the safety header.
- Do not install a 4-way mixing valve; the boiler is for hot water heating only.
- Connect the system per the piping diagram on page 45 of the manual.
Applies to: CA3B Dual Fuel 2.5 to 6.0
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 installation instructions, p. 15. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.