Condensate drain installation and neutralization

Vitodens 200-W, B2HB

What is going on

Condensate from the boiler and flue pipe is acidic (pH 3 to 4). It must go to the drain through a trap, and a neutralizer is used where local code requires it.

Check in this order

  1. Run the condensate drain pipe with a continuous fall toward the drain.
  2. Use corrosion-resistant materials only, such as braided hose. Do not use galvanized pipe or copper-containing fittings.
  3. Install a trap in the drain to stop flue gas leakage, and make the outlet visible with a stench trap.
  4. If the boiler condensate outlet is below the drain, install a condensate pump.
  5. If a neutralizer is used, vent the pipe between the siphon trap and the neutralizer.
  6. Check the neutralizer granulate level several times in the first year to set the refill interval. Treated water should be above pH 6.5 when discharged.
  7. Confirm local waterworks and waste water rules before installing the neutralizer.

Applies to: B2HB 19 to 57, 68 to 199

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitodens 200-W B2HB technical data manual, p. 20. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.