Wire one combustion air device to several boilers through the common interface
What is going on
A single combustion air device on a multiple boiler system needs a Common Combustion Air Interface. Each boiler gets its own adaptor.
Check in this order
- Install a Combustion Air Device Adaptor on each boiler (part 7134 563).
- Install the Common Combustion Air Device Interface (part 7134 604) as its manual says.
- Wire the interconnecting cable between the interface and each boiler adaptor. Use field-supplied wire.
- Use AWG 14 wire, rated 120 VAC, max 5 FLA.
Applies to: Multiple boiler systems with a shared combustion air device
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 100 GC1 / Vitocontrol-S installation manual, p. 57. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.