Viessmann · Boiler troubleshooting

First-stage burner enable contact (basic load)

Vitotronic 100

What is going on

Dry contact on plug aVD that switches the first-stage burner on or off.

Check in this order

  1. Connect a dry contact across terminals 1 and 2 of plug aVD.
  2. Contact closed the first-stage burner switches on. Boiler water temperature is limited by the electronic max limit (coding 06) if that is set below the mechanical high limit R.
  3. Contact open the first-stage burner switches off.

Applies to: Vitocrossal 300 with external modulation controller

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitotronic 100 GC1 installation manual, p. 64. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.