Viessmann · Boiler troubleshooting
First-stage burner enable contact (basic load)
What is going on
Dry contact on plug aVD that switches the first-stage burner on or off.
Check in this order
- Connect a dry contact across terminals 1 and 2 of plug aVD.
- Contact closed the first-stage burner switches on. Boiler water temperature is limited by the electronic max limit (coding 06) if that is set below the mechanical high limit R.
- Contact open the first-stage burner switches off.
Applies to: Vitocrossal 300 with external modulation controller
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitotronic 100 GC1 installation manual, p. 64. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.