Viessmann · Boiler troubleshooting

Simplified flue system leak check

Vitodens 222-F

What is going on

Checks the balanced flue annular gap for leaks by measuring combustion air.

Check in this order

  1. Measure the CO2 concentration of the combustion air in the coaxial gap of the air intake pipe using measuring port A on the vent adaptor.
  2. Accept the vent as sufficiently leak-proof if CO2 is no higher than 0.2% or O2 is no lower than 20.6%.
  3. If CO2 is higher or O2 is lower, check the venting system thoroughly.

Applies to: Vitodens 222-F B2TB 19, 35, 68, 125

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 222-F B2TB service instructions, p. 22. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.