Navien · Boiler troubleshooting

Ignition failure from flame rod or igniter buildup

NCB-H

What is going on

Ignition failures can happen when dirt or white powdery residue builds up on the flame rod. If ignition keeps failing, clean the flame rod. A new igniter gasket is required when the igniter is reinstalled, because a reused gasket can leak gas.

Likely causes

  • Buildup of dirt or white powdery residue on the flame rod (sensor)

Check in this order

  1. Turn off the power to the unit.
  2. Remove the igniter.
  3. Clean the flame rod with emery cloth and note the white powdery residue on the sensor.
  4. Reinstall the igniter with a new igniter gasket. Never reuse the old gasket.
  5. Turn the power back on and check ignition during operation.
  6. If ignition failure continues, contact Navien technical support.

Applies to: NCB-H series

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NCB-H emergency kit quick guide, p. 1. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.