Viessmann · Boiler troubleshooting
Fill condensate trap with water
What is going on
Fill the condensate trap before start-up so flue gases cannot pass through the drain. Close the main gas supply before removing the front panel.
Check in this order
- Close the main gas supply valve.
- Remove the accessories connection box cover.
- Loosen the bottom screws (do not remove them completely) and slide out the front enclosure panel.
- Remove retaining clip A from condensate trap B.
- Disconnect condensate trap B and fill it with water.
- Reinstall condensate trap B and secure with retaining clip A.
- Reinstall the front enclosure panel and keep the front cover on before operating the boiler.
Applies to: Vitodens 200-W B2HB 45, 57, 160, 199
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitodens 200-W B2HB 45, 57, 160, 199 service instructions, p. 15. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.