Weil-McLain · Boiler troubleshooting

Check burner flame (annual startup)

Ultra Series 4

What is going on

Inspect the flame through the observation window. Clean or replace the burner if the flame is poor at high or low fire.

Likely causes

  • Dirty or fouled burner
  • Damaged burner gasket
  • Loose burner retainer tabs

Check in this order

  1. Look at the flame through the observation window (procedure on page 40) at high fire and low fire.
  2. If the flame is unsatisfactory, shut off the boiler and let it cool.
  3. Remove the burner and clean it with a vacuum or compressed air. Do not use compressed air indoors.
  4. Remove the heat exchanger cover plate (page 125) to reach the burner.
  5. When refitting, check the gasket is good and correctly placed.
  6. After tightening the three retainer screws, bend up the retainer tabs.
  7. Reattach the cover plate per Figure 126 (page 126) or Figure 128 (page 127), then retest the boiler.

Applies to: Ultra 80, 105, 155, 230, 299, 399

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Ultra Series 4 gas-fired water boiler manual, p. 112. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.