Viessmann · Boiler troubleshooting

Boiler water temperature control

Vitocrossal 300 CA3B

What is going on

Burner modulates to hold the set boiler water temperature. The setpoint is the highest demand from heating circuits, LON, external demand, or DHW.

Check in this order

  1. Check the set supply temperatures of heating circuits on the control unit and LON.
  2. Check the external demand input if used.
  3. When heating the DHW tank, the boiler setpoint is 36°F (20 K) above the set DHW temperature.
  4. Adjust the DHW offset with coding 60 in the DHW group if needed.

Applies to: CA3B boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 service instructions, p. 38. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.