Viessmann · Boiler troubleshooting

Wiring the Versatronik 10.WB1 to a space heating zone controller

Versatronik 10.WB1

What is going on

The Versatronik space heating pump output is used as a control signal to the field zone controller. Zone pumps or valves only run on a zone call while the Versatronik output is on. This setup is for an outdoor reset application with no room thermostat.

Likely causes

  • No signal output from the Versatronik means the zone controller will not start any zone on a thermostat call

Check in this order

  1. Disconnect power from the Versatronik 10.WB1 and the zone control.
  2. Remove the ZC/ZR jumper from the zone controller.
  3. Connect the L output from the Versatronik 10.WB1 space heating pump to ZC on the zone controller.
  4. Power both devices and test operation.

Applies to: Boiler with Versatronik Como OT and outdoor reset, no room thermostat

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Versatronik 10.WB1 installation manual, p. 16. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.