Navien · Boiler troubleshooting

Air removal from the system piping

NCB700

What is going on

Air vents and bleeders must be placed around the system to purge air during commissioning. An air separator or air eliminator must be fitted, usually higher in the system where there is guaranteed positive pressure, such as near the water fill and expansion tank.

Likely causes

  • Air trapped in the system water

Check in this order

  1. Place air vents and bleeders at high points across the system.
  2. Install an air separator or eliminator and follow its installation instructions.
  3. Locate the air removal device where pressure is guaranteed positive, near the water fill and expansion tank.
  4. Use straight pipe with at least 1/2 in (12 mm) inside diameter on the upstream side of all pumps.
  5. Provide an expansion tank per the guidance on p. 22.
  6. In Massachusetts, install a vacuum relief valve in the cold water line per 248 CMR. Similar rules apply in New Jersey.

Applies to: NCB700 system piping

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NCB700 installation and operation manual, p. 29. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.