Weil-McLain · Boiler troubleshooting
Fill condensate trap with water
What is going on
The condensate trap must hold water whenever the boiler runs. If it is dry, flue gas can escape through the condensate drain.
Likely causes
- Trap not filled at startup
- Trap dry after cleaning or service
Check in this order
- Fill the trap with fresh water through the inspection caps near the flue connection on the piping end.
- To remove the trap, loosen the two stainless steel hose clamps on the flexible coupling.
- Slide the coupling off the 1 inch PVC pipe connected to the trap.
- Loosen the trap inlet connection, remove the trap and flush it.
- Refit the trap, fill it with fresh water, reconnect the coupling and tighten the clamps.
Applies to: SlimFit Series 2 boilers
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 81. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.