Weil-McLain · Boiler troubleshooting
Zoning with zone valves (three zones and system circulator)
What is going on
Zone valves are controlled by relays from the boiler control outputs. Input 1 is used to run the system circulator, not a thermostat.
Check in this order
- Install a by-pass pressure regulating valve in the system. Flow can occur with zone valves closed, which can cause severe injury, death or property damage if omitted.
- Review wiring information in Sections B and C (pages 72 and 73).
- Wire space heating thermostats to Inputs 2, 3 and 4 and assign them to PRIORITY 2 with the matching heating system type.
- Keep the factory default settings for the heating system type, or change if needed.
- Assign Input 1 to AUX PUMP/OUTPUT, then select the INPUTS PRIORITY SETTING when prompted for output activation timing so the system pump runs when any zone calls for heat.
- Confirm Priority 2 RUN AUX PUMP/OUT is set to YES.
- Do not use J17-1 and J17-2 for a wired connection, because they are used to run the system circulator.
- Zone valves can be 120 Vac or 24 Vac. A 24 Vac valve needs a relay with a 24 Vac coil from the transformer. Outputs 1 to 3 feed Zones 1 to 3 and J4-1 to J4-4 feed the system circulator.
Applies to: SVF 500/600 boilers zoned with zone valves
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SVF 500/600 Series 1 boiler manual, p. 81. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.