Zoning with zone valves (three zones and system circulator)

SVF 500/600 Series 1

What is going on

Zone valves are controlled by relays from the boiler control outputs. Input 1 is used to run the system circulator, not a thermostat.

Check in this order

  1. Install a by-pass pressure regulating valve in the system. Flow can occur with zone valves closed, which can cause severe injury, death or property damage if omitted.
  2. Review wiring information in Sections B and C (pages 72 and 73).
  3. Wire space heating thermostats to Inputs 2, 3 and 4 and assign them to PRIORITY 2 with the matching heating system type.
  4. Keep the factory default settings for the heating system type, or change if needed.
  5. Assign Input 1 to AUX PUMP/OUTPUT, then select the INPUTS PRIORITY SETTING when prompted for output activation timing so the system pump runs when any zone calls for heat.
  6. Confirm Priority 2 RUN AUX PUMP/OUT is set to YES.
  7. Do not use J17-1 and J17-2 for a wired connection, because they are used to run the system circulator.
  8. Zone valves can be 120 Vac or 24 Vac. A 24 Vac valve needs a relay with a 24 Vac coil from the transformer. Outputs 1 to 3 feed Zones 1 to 3 and J4-1 to J4-4 feed the system circulator.

Applies to: SVF 500/600 boilers zoned with zone valves

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF 500/600 Series 1 boiler manual, p. 81. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.