Connect combustion air blower through common interface

Vitotronic 100 GC1Vitotronic 300-K MW1S

What is going on

Wire the shared blower on a multiple boiler system.

Check in this order

  1. Disconnect power to the control and burner.
  2. Wire the blower motor (120 VAC, 5 FLA max.) to the common combustion air device interface.
  3. Wire the proving switch (120 VAC rated) and the 120 VAC supply as shown.
  4. Provide disconnect means and overcurrent protection as local codes require.
  5. Select the blower fuse using the blower manual's current rating.

Applies to: Multiple boiler system, shared blower

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 100 GC1 / 300-K MW1S installation, p. 43. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.