System layout with three zone circuits and low-loss header
What is going on
Layout for DHW production plus three zone circuits. Total flow of the circuits can exceed the boiler's maximum flow, so a low-loss header is strongly recommended.
Check in this order
- Fit a low-loss header; it is available as an accessory.
- Use the AM1 extension module for zone circuits 2 and 3.
- Use a zone thermostat with dry contact for each zone circuit.
- Where the underfloor circuit needs low temperature, use a 3-way mixing valve with the mixing valve accessory kit.
- For underfloor tubing without an oxygen diffusion barrier, install system separation.
- Use corrosion-resistant materials on the secondary side of the heat exchanger.
Applies to: Vitodens 200-W, B2HA/B 80 to 100, 285 to 352
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitodens 200-W B2HA 80 to 100, 285 to 352 installation manual, p. 41. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.