Viessmann · Boiler troubleshooting
Bus communication problems
What is going on
Controller and bus devices do not communicate correctly.
Likely causes
- Bus or sensor lines run too close to mains cables.
- Bus supply voltage is too low.
- Poles or switches are wrong.
Check in this order
- Check the bus lines and sensor lines run separately, away from mains cables.
- Check the bus feed at least 8 V DC must be measured between the + and - terminals of the BUS connector (connectors 18 and 19).
- If the bus voltage is lower than 8 V DC, install an external power supply.
- Check the communication symbol in the display or in Service / Communic MM 1.
Applies to: Versatronik 200 BUS network
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Versatronik 200 installation and operating manual, p. 166. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.