Viessmann · Boiler troubleshooting

Remove the burner tube and mounting plate

Vitocrossal 300 CA3B Dual Fuel

What is going on

A lifting device is required. Secure the lifting chains at the 3 marked points on the frame of the upper burner section.

Check in this order

  1. Attach lifting chains at the 3 marked points A on the upper burner frame.
  2. Remove the 8 nuts from the combustion chamber cover plate.
  3. Lift out the mounting plate with the burner tube using the lifting device and its instructions.
  4. Keep tools and objects out of the combustion chamber.

Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 service instructions, p. 70. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.