Viessmann · Boiler troubleshooting
Check the outdoor temperature sensor
What is going on
Check the sensor resistance against the outdoor temperature. Replace the cable or sensor if the readings are far from the curve.
Likely causes
- Sensor reading differs severely from the curve.
Check in this order
- Remove plug.
- Measure sensor resistance at terminals 1 and 2 of the plug.
- Compare with the table -10 °C / 14 °F about 480, 0 °C / 32 °F about 500, 20 °C / 68 °F about 546.
- If readings deviate severely, disconnect the cores from the sensor and repeat the measurement; compare with the actual temperature.
- Replace the cable or the outdoor temperature sensor depending on the result.
- Scan the actual temperature.
Applies to: Outdoor temperature sensor 7820 148
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 300 GW2 installation and service instructions, p. 99. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.