Viessmann · Boiler troubleshooting
Check the neutralization unit (if fitted)
What is going on
Applies only where a neutralization unit is installed. The granulate is used up as it neutralizes the condensate. The red marking shows the minimum fill level. A pH strip must be supplied by the installer.
Likely causes
- Condensate pH below 6.5
- Contaminated neutralization unit
- Granulate below the red minimum mark
Check in this order
- Check the condensate pH with a pH measuring strip.
- If the pH is below 6.5, replace the granulate.
- If the unit is contaminated, rinse it with tap water.
- Add granulate up to the marked level.
Applies to: Neutralization unit
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 222-F B2TB 19, 35, 68, 125 Service Instructions, p. 25. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.