Weil-McLain · Boiler troubleshooting

Additional limit controls and external limit wiring

EGPEGSeries 7

What is going on

ASME installations may need a manual reset high temperature limit in the supply piping. Systems with low-temperature circuits should protect them with external limits wired to the Unity-CI control P4 terminals.

Check in this order

  1. If ASME applies, install a manual reset high temperature limit in the system supply piping between the boiler and its isolation valve. Set it to no more than 240°F.
  2. Note that the Unity-CI operating limit shuts the boiler down at 210°F or lower, depending on the set value.
  3. For a manual reset external limit, wire series isolated contacts to P4 terminal 1 by cutting and splicing at mark ‹1›.
  4. For an automatic reset external limit, wire series isolated contacts to P4 terminal 3 by cutting and splicing at mark ‹2›.
  5. If a manual reset limit is used, set the Unity-CI boiler limit at least 20°F below the external manual reset limit (for example, no higher than 180°F for a 200°F external limit).

Applies to: EG / PEG Series 7 water boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: EG / PEG Series 7 boiler manual, p. 33. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.