Weil-McLain · Boiler troubleshooting
Additional limit controls and external limit wiring
What is going on
ASME installations may need a manual reset high temperature limit in the supply piping. Systems with low-temperature circuits should protect them with external limits wired to the Unity-CI control P4 terminals.
Check in this order
- If ASME applies, install a manual reset high temperature limit in the system supply piping between the boiler and its isolation valve. Set it to no more than 240°F.
- Note that the Unity-CI operating limit shuts the boiler down at 210°F or lower, depending on the set value.
- For a manual reset external limit, wire series isolated contacts to P4 terminal 1 by cutting and splicing at mark ‹1›.
- For an automatic reset external limit, wire series isolated contacts to P4 terminal 3 by cutting and splicing at mark ‹2›.
- If a manual reset limit is used, set the Unity-CI boiler limit at least 20°F below the external manual reset limit (for example, no higher than 180°F for a 200°F external limit).
Applies to: EG / PEG Series 7 water boilers
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: EG / PEG Series 7 boiler manual, p. 33. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.