Condensate trap installation

SVF 500/600 Series 1

What is going on

Install the condensate trap in the correct vertical position so flue gas cannot escape through the drain.

Check in this order

  1. Keep the condensate trap vertical. Do not wedge it against the ground or any other object.
  2. Slide the end of the plastic trap onto the drain on the back of the boiler.
  3. Tighten a hose clamp to secure the trap to the drain pipe.
  4. Secure the condensate bracket to the boiler base.
  5. Slide the PVC tee through the bracket.
  6. Loosely fit the second hose clamp over the right side of the trap, slide the trap over the tee and up to the bracket, then tighten the clamp.

Applies to: SVF 500/600 boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain SVF 500/600 Series 1 boiler manual, p. 61. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.