Weil-McLain · Boiler troubleshooting
Condensate trap installation
What is going on
Install the condensate trap in the correct vertical position so flue gas cannot escape through the drain.
Check in this order
- Keep the condensate trap vertical. Do not wedge it against the ground or any other object.
- Slide the end of the plastic trap onto the drain on the back of the boiler.
- Tighten a hose clamp to secure the trap to the drain pipe.
- Secure the condensate bracket to the boiler base.
- Slide the PVC tee through the bracket.
- Loosely fit the second hose clamp over the right side of the trap, slide the trap over the tee and up to the bracket, then tighten the clamp.
Applies to: SVF 500/600 boilers
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain SVF 500/600 Series 1 boiler manual, p. 61. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.