Viessmann · Boiler troubleshooting
Two-stage burner dew-point protection
What is going on
The burner should go to full (second-stage) input when boiler water falls below the minimum to protect against condensation and corrosion. The burner must not be held in first-stage operation during summer.
Likely causes
- Boiler water below 140 °F (60 °C) causes condensation.
Check in this order
- Set the burner so it is not limited to first-stage operation in summer.
- Confirm the burner switches to second stage when boiler water falls below 140 °F (60 °C).
- Set the first-stage minimum inputs to the table values when used with a Vitotronic control.
Applies to: Two-stage burners
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitorond 200 VD2A service instructions, p. 14. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.