Viessmann · Boiler troubleshooting

Two-stage burner dew-point protection

Vitorond 200 VD2A

What is going on

The burner should go to full (second-stage) input when boiler water falls below the minimum to protect against condensation and corrosion. The burner must not be held in first-stage operation during summer.

Likely causes

  • Boiler water below 140 °F (60 °C) causes condensation.

Check in this order

  1. Set the burner so it is not limited to first-stage operation in summer.
  2. Confirm the burner switches to second stage when boiler water falls below 140 °F (60 °C).
  3. Set the first-stage minimum inputs to the table values when used with a Vitotronic control.

Applies to: Two-stage burners

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitorond 200 VD2A service instructions, p. 14. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.