Flue outlet and flue gas test point

Vitorond 200 VD2

What is going on

Connect the flue outlet to the chimney and provide a test point for combustion analysis.

Check in this order

  1. Connect the flue outlet with the shortest possible run, sloping slightly up toward the chimney. Avoid sharp bends.
  2. The flue outlet is 12 in. (300 mm) outside diameter.
  3. Drill a test hole of about 10 mm (3/8 in.) in the side of the vent pipe about two to three vent diameters from the boiler flue collar.
  4. Seal and insulate the vent pipe.
  5. Make sure the chimney size is designed for the actual boiler model and input. The boiler outlet size does not set the breeching or chimney size.

Applies to: Vitorond 200 VD2 320 to 1080

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitorond 200, VD2 Series 320 to 1080 Installation Instructions, p. 24. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.