Viessmann · Boiler troubleshooting
Replacing the plate heat exchanger (B1KE)
What is going on
Removal, inspection and refitting of the brazed plate heat exchanger.
Likely causes
- Scaling on DHW connections
- Contamination on heating water connections
Check in this order
- Close the gas shutoff valve and isolate the power supply. Confirm the system is not live.
- Shut off and drain the boiler on the heating water and DHW sides.
- Undo the screws and remove the plate heat exchanger.
- Remove and dispose of the gaskets.
- Check the DHW side connections for scaling and clean or replace the exchanger as needed.
- Check the heating water side connections for contamination and clean or replace the exchanger as needed.
- Install the plate heat exchanger in reverse order with new gaskets, making sure connections and gaskets are seated correctly.
- Tighten the screws to the specified torque (see setting).
- Check all water side connections for tightness.
Applies to: B1KE plate heat exchanger
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitodens 100-W B1HE/B1KE installation/service manual, p. 86. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.