Viessmann · Boiler troubleshooting

Replacing the plate heat exchanger (B1KE)

Vitodens 100-W B1HE/B1KE

What is going on

Removal, inspection and refitting of the brazed plate heat exchanger.

Likely causes

  • Scaling on DHW connections
  • Contamination on heating water connections

Check in this order

  1. Close the gas shutoff valve and isolate the power supply. Confirm the system is not live.
  2. Shut off and drain the boiler on the heating water and DHW sides.
  3. Undo the screws and remove the plate heat exchanger.
  4. Remove and dispose of the gaskets.
  5. Check the DHW side connections for scaling and clean or replace the exchanger as needed.
  6. Check the heating water side connections for contamination and clean or replace the exchanger as needed.
  7. Install the plate heat exchanger in reverse order with new gaskets, making sure connections and gaskets are seated correctly.
  8. Tighten the screws to the specified torque (see setting).
  9. Check all water side connections for tightness.

Applies to: B1KE plate heat exchanger

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitodens 100-W B1HE/B1KE installation/service manual, p. 86. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.