Weil-McLain · Boiler troubleshooting

Removing a boiler from an existing common vent (vent system verification)

SlimFit Series 3

What is going on

Once the SlimFit is removed from a shared vent, remaining appliances may not vent properly if the flue is oversized. Test each remaining appliance this way.

Likely causes

  • Vent oversized for the remaining appliances after the old boiler is removed

Check in this order

  1. Seal any unused openings in the common vent.
  2. Visually inspect the vent for correct size, horizontal pitch, blockage, leakage, corrosion or other unsafe conditions.
  3. Close building doors and windows, and doors to other spaces. Run clothes dryers, non-vented appliances and exhaust fans (range hood, bath) at maximum speed. Do not run a summer exhaust fan. Close fireplace dampers.
  4. Run one remaining appliance alone with its thermostat calling for continuous operation.
  5. After 5 minutes of main burner operation, test the draft hood relief opening for spillage using a flame, candle or smoke.
  6. When each appliance vents correctly, return doors, windows, fans, dampers and other appliances to their normal state.
  7. If any appliance fails, correct the common vent to meet the National Fuel Gas Code (ANSI Z223.1) or B149.1/B149.2 in Canada, usually by resizing toward the minimum size from the code tables.

Applies to: Existing common vent systems replaced by SlimFit boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit Series 3 boiler manual 550-100-559/0725, p. 23. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.